Rated Voltage : 0.6/1 kV
Ref. Specification : IEC 60502-1 (Other Specification are available on request)
Symbol
Applicable Standard : Other Specification are available on request
Construction
Annealed Copper Conductor
Extruded XLPE Insulation
Extruded PVC Inner Sheath
Extruded Lead Sheath
Extruded PVC Separation Sheath
Galvanized Steel Tape Armour
Extruded PVC Outer Sheath
| No of Core | Size | Conductor | Nom. Wall Thickness | Approx. Overall Diameter | Approx. Net Weight | Standard Length | Max. DC Conductor Resistance at 20 C | Minimum Insulation Resistance at 20 C | Maximum Continous Current Carrying Capacity | Maximum Short Circuit Current for 1 Sec. | ||||
| Construction | No of Wire | Insulation | Lead Sheath | Outer Sheath | In Ground at 30 C | In Air at 30 C | ||||||||
| - | mm2 | - | - | mm | mm | mm | mm | kg/km | m | Ohm/km | M.Ohm.km | A | A | kA |
| 2 | 1.5 | re/rm | 1/7 | 0.7 | 1.2 | 1.8 | 17.9 | 789 | 1000 | 12.1 | 2500 | 33 | 27 | 0.21 |
| 2 | 2.5 | re/rm | 1/7 | 0.7 | 1.2 | 1.8 | 18.7 | 869 | 1000 | 7.41 | 2100 | 44 | 36 | 0.36 |
| 2 | 4 | re/rm | 1/7 | 0.7 | 1.2 | 1.8 | 19.7 | 975 | 1000 | 4.61 | 1800 | 58 | 48 | 0.57 |
| 2 | 6 | re/rm | 1/7 | 0.7 | 1.2 | 1.8 | 20.9 | 1106 | 1000 | 3.08 | 1500 | 72 | 61 | 0.85 |
| 2 | 10 | re/rm | 1/7 | 0.7 | 1.2 | 1.8 | 22.7 | 1328 | 500 | 1.83 | 1200 | 97 | 83 | 1.42 |
| 2 | 16 | rm | 7 | 0.7 | 1.3 | 1.8 | 24.9 | 1671 | 500 | 1.15 | 1100 | 128 | 113 | 2.27 |
| 2 | 25 | rm | 7 | 0.9 | 1.4 | 1.9 | 28.8 | 2248 | 500 | 0.727 | 1100 | 167 | 150 | 3.55 |
| 2 | 35 | rm | 7 | 0.9 | 1.4 | 1.9 | 31.0 | 2639 | 500 | 0.524 | 1000 | 201 | 186 | 4.97 |
| 2 | 50 | rm | 19 | 1.0 | 1.5 | 2.1 | 34.8 | 3314 | 500 | 0.387 | 900 | 239 | 226 | 7.10 |
| 2 | 70 | rm | 19 | 1.1 | 1.6 | 2.3 | 41.0 | 4709 | 500 | 0.268 | 900 | 295 | 290 | 9.94 |
| 2 | 95 | rm | 19 | 1.1 | 1.8 | 2.4 | 45.4 | 5956 | 500 | 0.193 | 800 | 355 | 353 | 13.49 |
| 2 | 120 | rm | 37 | 1.2 | 1.9 | 2.6 | 49.8 | 7139 | 500 | 0.153 | 800 | 404 | 413 | 17.04 |
| 2 | 150 | rm | 37 | 1.4 | 2.0 | 2.7 | 54.6 | 8528 | 250 | 0.124 | 800 | 458 | 468 | 21.30 |
Maximum Permissible Continous Conductor Temperature 90 C
Maximum Short Time Overload Temperature 30 C
Maximum Short Circuit Conductor Temperature 250 C
Standard Packing Wooden Drum