CU/PVC/OS/SWA/PVC

CU/PVC/OS/SWA/PVC

Cable Construction :

Conductor : Plain Annealed copper wire class 2 according to IEC 60228
Insulation   : Extruded PVC (Polyvinyl Chloride)
Overall Screen : Helically Overlapped Polyester Tape
Tinned Annealed Copper wire 0.5mm2 (20/0.18 mm)
Helically Overlapped Single coated Alumunium Tape contacted with drain wire
Helically Overlapped Polyester Tape
Inner Sheath   Extruded PVC Flame Retardant (Black)
Armour     Galvanized Steel Wire
Outer Sheath   Extruded PVC Flame Retardant (Black or requested by customer)
Pair Identification    
1 Pair   Black and White
Multi Pair       Black and White with numbering
Amount of halogen acid gas   Max 17% (IEC 60754-1)
Limiting oxygen index (LOI)     Min 30% (IEC 60332-3 annex B)
Sunlight resistance     UL 1581 section 1200
Oil resistance     ICEA S-82-552
Flame Retardant   IEC 60332-1
Flame propagation   IEC 60332-3 Cat. A, B, C
Designation Voltage   300 V & 500 V
Screen Resistance   Min. 1 MOhm/km
Insul Resistance   Min. 10 MOhm/km
Min. Bending Radius   6 x OD (fixed installation)
Temperature Rating     -40 C to 70 C
AC Test Voltage   300 V : 1000 V/1 min
500 V : 2000 V/1 min
Symbol      
Applicable Standard      
Other Specification are available on request  
Application    :        

Download Katalog  

CU/PVC/OS/SWA/PVC
      
Instrument Cable 300 V
BS EN 50288-7 : 2005     

Nominal Size

Number of Pair

Conductor

Insulation

Inner Sheath

Armoured

Outer Sheath

Approx OD of Cable

Approx. Cable Weight

Standard Length per Drum

No of Wire

Shape

Approx. dia.

Nom. Thickness

Nom. Thickness

Nom.Diameter

Nom. Thickness

mm2

-

-

-

mm

mm

mm

mm

mm

mm

kg/km

m

0.5

1

7

rm

0.90

0.4

1.0

0.90

1.3

10.8

231

1000

2

7

rm

0.90

0.4

1.0

0.90

1.4

13.5

341

1000

5

7

rm

0.90

0.4

1.0

0.90

1.4

14.8

408

1000

10

7

rm

0.90

0.4

1.1

0.90

1.5

18.2

572

1000

15

7

rm

0.90

0.4

1.2

1.25

1.6

21.6

845

1000

20

7

rm

0.90

0.4

1.3

1.25

1.7

23.8

1,008

1000

30

7

rm

0.90

0.4

1.4

1.25

1.8

27.5

1,297

1000

50

7

rm

0.90

0.4

1.6

1.6

1.9

34.1

2,041

1000

0.75

1

7

rm

1.11

0.4

1.0

0.90

1.3

11.4

259

1000

2

7

rm

1.11

0.4

1.0

0.90

1.4

14.6

400

1000

5

7

rm

1.11

0.4

1.1

0.90

1.5

16.3

489

1000

10

7

rm

1.11

0.4

1.2

1.25

1.6

21.0

816

1000

15

7

rm

1.11

0.4

1.3

1.25

1.7

24.1

1,036

1000

20

7

rm

1.11

0.4

1.4

1.25

1.7

26.7

1,251

1000

30

7

rm

1.11

0.4

1.6

1.25

1.9

31.1

1,640

1000

50

7

rm

1.11

0.4

1.8

1.6

2.1

38.7

2,580

1000

1.0

1

7

rm

1.29

0.4

1.0

0.90

1.3

11.6

268

1000

2

7

rm

1.29

0.4

1.0

0.90

1.4

15.0

426

1000

5

7

rm

1.29

0.4

1.1

0.90

1.5

16.8

537

1000

10

7

rm

1.29

0.4

1.2

1.25

1.6

21.7

903

1000

15

7

rm

1.29

0.4

1.3

1.25

1.7

24.9

1,154

1000

20

7

rm

1.29

0.4

1.4

1.25

1.8

27.7

1,400

1000

30

7

rm

1.29

0.4

1.6

1.6

1.9

33.0

2,040

1000

50

7

rm

1.29

0.4

1.8

1.6

2.1

40.2

2,940

500

1.5

1

7

rm

1.59

0.5

1.0

0.90

1.4

12.7

317

1000

2

7

rm

1.59

0.5

1.1

0.90

1.5

17.0

534

1000

5

7

rm

1.59

0.5

1.2

0.90

1.6

19.2

698

1000

10

7

rm

1.59

0.5

1.3

1.25

1.7

25.1

1,180

1000

15

7

rm

1.59

0.5

1.4

1.25

1.8

29.1

1,543

1000

20

7

rm

1.59

0.5

1.6

1.6

1.9

33.3

2,068

1000

30

7

rm

1.59

0.5

1.8

1.6

2.1

38.9

2,769

1000

50

7

rm

1.59

0.5

2.1

2.0

2.3

     

Tolerance of overall diameter : OD ≤ 20 mm : ± 1.0 mm, OD ≤ 40mm : ± 2mm, OD > 40 mm : ± 5%               
NOTE : Number of Pair other than above are also available

Nominal Size

Max DC Conductor Resistance at 20 C

Min Insulation Resistance at 20 C

AC Voltage test

sqmm

Ohm/km

M.Ohm.km

V / 1 min.

0.5

36.2

10

1,000

0.75

24.7

10

1,000

1.0

18.3

10

1,000

1.5

12.3

10

1,000

* Standard packing : wooden drum