MV-105 MC-HL 2.4 KV

MV-105 MC-HL 2.4 KV

Copper conductor, EPR Insulation with aluminium welded corrugated armoured and PVC sheated ( non shielded )

Construction
A. Compact circular stranded copper conductor
B. Extruded semiconductive compund conductor screen
C. Extruded EPR insulation
D. Copper grounding conductors
E. Polypropylene yarn filler & polyester tape binder
F. Aluminium welded corrugated armour
G. Extruded PVC 90°C grade outer sheath ( yellow colour )

Identification of Cores :

Phase   Identification by PE tape ( black, red, blue )
Grounding   Uninsulated
     

 

Symbol    :    MV-105 MC-HL 2.4 kV or CU/EPR/MC/PVC

Applicable Standard : Rated Voltage : 2,4 kV
Specification : ICEA S-93-639/NEMA WC74
UL 1072
Other Specification are available on request
Application : * Indoor and outdoor ( wet or dry location )
* Branch circuit for power distribution system
* Installation direct burial
* Installation cable tray
* Approved for classes I, II and division I and 2, class 1, zones 1 and 2

Download Catalog

No. of Core Size Conductor Grounding Conductor Thickness Insulation Thickness Insulation Out. Sheath Approx Overall Diameter Cable Approx Net. Weight Standard Length
Construction No. of Wire Nom. Thickness
  AWG/kcmil      No x Size (AWG) mm mm mm mm Kg/Km m
3 8 cm 7 3 x12 2.29 31.3 1.27 34.2 1345 1000
3 6 cm 7 3 x10 2.29 34.2 1.27 37.1 1643 1000
3 4 cm 7 3 x10 2.29 36.7 1.27 39.6 1979 1000
3 2 cm 7 3 x10 2.29 41.6 1.52 45.0 2734 500
3 1 cm 19 3 x 8 2.29 43.3 1.52 46.7 3145 500
3 1/0 cm 19 3 x 8 2.29 45.4 1.52 48.8 3574 500
3 2/0 cm 19 3 x 8 2.29 47.7 1.52 51.1 4079 500
3 4/0 cm 35 3 x 7 2.29 55.6 1.52 59.0 5711 500
3 250 cm 35 3 x 6 2.29 57.9 1.90 62.1 6578 500
3 350 cm 35 3 x 6 2.29 63.3 1.90 67.5 8310 500
3 500 cm 35 3 x 5 2.29 70.4 1.90 74.6 10900 500
3 750 cm 56 3 x 4 2.29 81.5 2.16 86.2 15461 300

Characteristics :


 

No. of Core Size Max. DC Conductor Resistance at 20o C   Max. AC Conductor Resistance at 90o C Max Pulling Tension Inductance Capacitance Impedance Current Carrying Capacity Short Circuit
Current at 1 sec
AC Voltage Test
Conductor Insulation Buried Direct in Ground
at 200 C
In a Cable Tray
at 400 C

In Air
at 400C

  AWG kcmil  Ohm / Km M.Ohm.km Ohm / Km Kg mH/km µF/km Ohm/km Ampere Ampere Ampere kA kA / 5 mins
3 8 2.011 2000 2.678 244 0.363 0.180 2.680 90 58 66 1.044 18
3 6 1,323 2000 1.683 388 0.332 0.205 1.686 115 77 88 1.661 18
3 4 0,830 2000 1.059 552 0.305 0.236 1.063 150 100 115 2.641 18
3 2 0,521 2000 0.666 813 0.280 0.275 0.672 190 135 154 4.200 18
3 1 0,415 2000 0.532 1055 0.269 0.297 0.539 215 155 180 5.258 18
3 1/0 0,328 2000 0.419 1294 0.258 0.324 0.427 245 185 205 6.684 18
3 2/0 0,261 2000 0.333 1581 0.248 0.352 0.342 280 210 240 8.400 18
3 4/0 0,164 2000 0.210 2457 0.230 0.421 0.222 360 285 320 13.368 18
3 250 0,139 2000 0.179 2917 0.224 0.449 0.192 395 315 355 15.773 18
3 350 0,099 2000 0.128 3980 0.213 0.515 0.145 475 390 440 22.123 18
3 500 0,070 2000 0.091 5628 0.202 0.598 0.111 570 475 545 31.546 18
3 750 0,046 2000 0.063 8381 0.192 0.712 0.087 700 585 685 47.455 18